139-0600-00 12/1/13RemotePowerControllerfor MobileDistributionInstruction BulletinRetain for future use.LynTec RPCM

Seite 2 - Class A FCC Statement

139-0498-0110Chapter Four--Wiring10Emergency Shutdown Wiring:To connect your  re alarm or emergency management system to the RPCM, follow these steps

Seite 3 - Table of Contents

139-0498-01.11 11Chapter Four--WiringFigure 4-2: Control WiringInstall and connect a standard Cat. 5e cable from the facility network to the Controll

Seite 4 - 139-0498-01.4

139-0498-0112Chapter Four--Wiring12INITIAL POWER UP PROCEDUREWith cover o and breakers visible, turn on the panel main breaker and the Controller P

Seite 5 - Chapter 1--Introduction

139-0498-01.13 13Chapter Five--Control SetupChapter 5--Control Setup (Web Page)OVERVIEWSTATUS CONTROLSETUPSUPPORTThere are 5 main tabs on your RPC web

Seite 6 - Table 1–1

139-0498-01.14Chapter Five--Control Setup14SetupSETUP HOMETo set the username and password for your panel, click the Setup tab. The Setup Home tab sho

Seite 7 - 139-0498-01.7 7

139-0498-01.15 15Chapter Five--Control SetupNetwork setupFigure 5-2--Network SettingsFigure 5-2 shows the network settings portion of the Network setu

Seite 8 - INTRODUCTION

139-0498-01.16Chapter Five--Control Setup16Figure 5-3: Interface optionsNetBios NameThe NetBios name defaults to LynTecRPC. Each master panel in you

Seite 9 - Chapter 4--Wiring

139-0498-01.17 17Chapter Five--Control SetupDMXFor DMX operation use the following steps:The RPCM allows up to four di erent sets of DMX starting add

Seite 10 - Chapter Four--Wiring

139-0498-01.18Chapter Five--Control Setup18Panel SetupBREAKER SETUPThis section explains how to setup your panel and motorized breakers for remote ope

Seite 11 - 139-0498-01.11 11

139-0498-01.19 19Chapter Five--Control SetupZONE SETUPBreakers can be controlled individually or arranged into zones. Breakers in zones can be toggle

Seite 12 - PROCEDURE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service, or maintain

Seite 13 - Chapter Five--Control Setup

139-0498-01.20Chapter Five--Control Setup202. Name the Zone. (Figure 5-7)3. Choose Grouped, Sequenced, DMX or sACN operation. Note: DMX and sACN ma

Seite 14 - SETUP HOME

139-0498-01.21 21Chapter Five--Control Setup5. Select a breaker to add to the zone by clicking on the breaker you want to add. Only motorized breake

Seite 15 - Network setup

139-0498-01.22Chapter Five--Control Setup228. Click the “Close” button when  nished to save. Or, click “Remove” to remove the breaker from the zone

Seite 16 - 139-0498-01.16

139-0498-01.23 23Chapter Five--Control SetupNumbering and addressingThe RPC system allows the user to choose top/bottom panel numbering or left/right

Seite 17 - 139-0498-01.17 17

139-0498-01.24Chapter Five--Control Setup24Global Control Preferences The following features can be selected for additional system  exibilityFigure 5

Seite 18 - Panel Setup

139-0498-01.25 25Chapter Five--Control SetupSelecting breakers for Emergency Shutdown, Emergency Lighting or BrownoutFigure 5-17Select breakers to act

Seite 19 - ZONE SETUP

139-0498-01.26Chapter Five--Control Setup26Schedule SetupFollow these steps to set a schedule (not applicable for DMX or sACN).1. Enable Schedules in

Seite 20

139-0498-01.27 27Chapter Six--OperationChapter Six: Operating your RPCMFigure 6-1Using the built-in web pageTo operate the RPC using the built in web

Seite 21 - Click on the green oval

139-0498-01.28Appendix A28Appendix A--TCP/IP ProtocolTCP/IP PROTOCOLTCP/IP communications and control via a third party control system is facilitated

Seite 22

139-0498-01.29 29Appendix AEvents include:Event 1 = “All Breakers ON”Event 2 = “All Breakers OFF”Event 3 = “Hurry OFF” zips all breakers o fast.Even

Seite 23 - GLOBAL PREFERENCES

139-0498-01.3 3RPC ControllerTable of ContentsContentsChapter 1--Introduction ...

Seite 24 - 139-0498-01.24

139-0498-01.30Appendix B--Troubleshooting/FAQ30HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH• This equipment must be installed and serviced only

Seite 25 - 139-0498-01.25 25

139-0498-01.31 31Appendix B--Troubleshooting/FAQTable C-1: RPC Controller TroubleshootingCondition Possible Causes SolutionsFront Panel LCD and statu

Seite 26 - 139-0498-01.26

139-0498-01.32Appendix C32Appendix C--RPC System ComponentsThe LynTec system consists of control buses, a panelboard, remotely operated circuit breake

Seite 27 - Chapter Six--Operation

139-0498-01.33 33Appendix CPower Supply The Power Supply connects to a 15A non-motorized breaker and provides 24VDC, 3A power to the RPC controller.F

Seite 28 - Appendix A--TCP/IP Protocol

139-0498-01.34Appendix C34Control Module The RPC Control Module provides control logic for theoperation of a RPC system. The controller uses remotelyo

Seite 29 - Appendix A

139-0498-01.35 35Appendix CAuxiliary Power Supply 24 Vdc (200mA maximum Current)Communication Interface RJ-45 (8P8C) TCP/IP/sACN/Web Server/100 Base T

Seite 30 - Appendix B--Troubleshooting

139-0498-01.36Appendix D36Appendix D--RPC System Diagrams and SchematicsNEUTRALCCBBAALR164403910152122272833343918642511121723242930353641142381781319

Seite 31

139-0498-01.37 37Appendix DLOW VOLTAGE SECTIONINTERIOR SPACEREAR PANELFRONT PANEL DISPLAYRPC CONTROLLER24V BUFFERBCPM-APOWER MONITORGN42 POSITIONCIRCU

Seite 32 - Components

139-0498-01.4RPC ControllerTable of ContentsAppendix A--TCP/IP Protocol ...

Seite 33 - Appendix C

139-0498-01.5 5Chapter One--OverviewThis bulletin explains how to connect and operate the LynTec Remote Power Controller-Mobile Power Distribution Cab

Seite 34 - 139-0498-01.34

139-0498-01.66Chapter One--OverviewFront Panel Overview Figure 1–1 shows the parts of the RPCM front panel. A brief description of each part follows

Seite 35 - Speci cations

139-0498-01.7 7Chapter Two--Safety PrecautionsChapter Two--Safety PrecautionsThis chapter contains important safety precautions that must be followed

Seite 36 - Diagrams and Schematics

139-0498-01.8Chapter Three--Quick Start Guide8Steps Reference1. Connect the RPCM to 120/208V power source See appropriate instruction bulletins.Chapt

Seite 37 - RPCM BLOCK DIAGRAM

139-0498-01.9 9Chapter Four--WiringChapter 4--Wiring1. In this order, connect ground, neutral and phase feeds to rear panel.2. Verify the presence o